AC Current Meter – 150 Amp

Clear
SKU: N/A Category:
  • Description
  • Product Specification
  • Documentation
  • Applications

Description

Senseit wireless AC Current Meters measure the RMS current of an alternating current (AC) system using a current transformer (CT) that wraps around the “hot” wire of a two wire (hot, common, ground(optional)) power system. The sensor reports Minimum RMS current, maximum RMS current, average RMS current, and amp hours to the iSenseit system. The iSenseit system is capable of generating watt hour or kilowatt hour readings as well.

The standard version of this sensor is powered by two replaceable 1.5 V AA sized batteries (included with purchase). This sensor is also available with a line power option. The line powered version of this sensor has a barrel power connector allowing it to be powered by a standard 3.0 – 3.6 V power supply (Included with Line Power option upgrade). The line powered version also uses two standard 1.5 V AA batteries as backup for uninterrupted operation in the event of line power outage.

Power options must be selected at time of purchase, as the internal hardware of the sensor must be changed to support the selected power requirements.

WARNING: This AC current meter is for monitoring AC voltage only. Do Not Use with DC voltage.

What does this wireless sensor’s data look like in software?

Product Features

  • Measures amp hours, max RMS current, min RMS current, and average RMS current.
  • Capable of generating Watt Hour or Kilowatt Hour readings using iSenseit.
  • Data logging for accumulated amp hour readings.
  • Can notify based on current levels or changes in current levels.
  • Measures current from 0 to 150 Amps.

What’s in the box?

  • Wireless Sensor
  • Mounting Hardware
  • 2 x AA Batteries

AC Current Meter Specifications

Accuracy+/- 2% @ 2 to 150 Arms, +/- .4 Arms @ < 15 Arms
Current Transducer Frequency Range50 – 100 Hz
Absolute Max CT Current200 Amps RMS (Arms)
Maximum Accurate CT Current150 Arms
Calibrated Accuracy with Appropriate Offset+/- 1% @ 2 to 150 Arms, +/- .2 Arms @ < 2 Arms
Offset Limits-1.27 to + 1.27 Arms (default set to +.3 Arms)
Measurement Resolution~.1 Arms

AA Specifications

Battery Type2 Replaceable AA 1.5 V Batteries
Dimension4.375 in x 2.470 in x 1.12 in
Sensing Element2.0 - 3.6 V (2 x AA 1.5V Batteries or Optional Power Supply)
Device Range250 - 300 ft. non-line-of-sight device range*
Battery LifeAt 1 hour heartbeat setting, included AA batteries will typically last 3-4 Years. **
Max Operating Temperature Using AA Alkaline-18°C to 55°C (0°F to 130°F)
Max Operating Temperature Using AA Lithium-40°C to 60°C (-40°F to 140°F)
Optimal Battery Operating Temperature+10°C to +50°C (+50°F to +122°F)
Enclosure MaterialABS

900 MHz Specifications

Operating Frequency900 MHz Operating Frequency
CertificationsComplies with Part 15 of the FCC Rules. (FCC ID: ZTL-RFSC1)
Complies with Industry Canada standards. (IC: 9794A-RFSC1)
  • Current Monitoring
  • Current Usage
  • Amperage Monitoring
  • Amp Hour Meter
  • Watt Hour Meter
  • Kilowatt Hour Meter